The DLM-080 FUTURE Digital Recorder – User’s Manual
26.11.2004
30
F37
2 0..25.5
The controller’s upper hysteresis value for
CHANNEL 4
.
similarly as before
F38
2 0..25.5
The controller’s lower hysteresis value for
CHANNEL 5
.
similarly as before
F39
2 0..25.5
The controller’s upper hysteresis value for
CHANNEL 5
.
similarly as before
F40
2 0..25.5
The controller’s lower hysteresis value for
CHANNEL 6
.
similarly as before
F41
2 0..25.5
The controller’s upper hysteresis value for
CHANNEL 6
.
similarly as before
F42
2 0..25.5
The controller’s lower hysteresis value for
CHANNEL 7
.
similarly as before
F43
2 0..25.5
The controller’s upper hysteresis value for
CHANNEL 7
.
similarly as before
F44
2 0..25.5
The controller’s lower hysteresis value for
CHANNEL 8
.
similarly as before
F45
2 0..25.5
The controller’s upper hysteresis value for
CHANNEL 8
.
similarly as before
F46
0 0..2
Controller output definition for CHANNEL 1 F46=0 controller contact
normally closed (algorithm 1)
F46=1 controller contact
normally open (algorithm 2)
Cell value = 2 Æ 3-state
controller (according to
algorithm 3)
F47
0 0..2
Controller output definition for CHANNEL 2 as before
F48
0 0..2
Controller output definition for CHANNEL 3 as before
F49
0 0..2
Controller output definition for CHANNEL 4 as before
F50
0 0..1
Controller output definition for CHANNEL 5 F50=0 controller contact
normally closed (algorithm 1)
F50=1 controller contact
normally open (algorithm 2)
F51
0 0..1
Controller output definition for CHANNEL 6 as before
F52
0 0..1
Controller output definition for CHANNEL 7 as before
F53
0 0..1
Controller output definition for CHANNEL 8 as before
F54
0 0..13
Analogue input type definition and display range
definition for CHANNEL 1
Definition:
0 – PT-100 RANGE:
(- 99,0..400,0);
1 – RANGE OF HUMIDITY
FROM PSYCHROMETER:
0..99
2 – NOT USED
3 – RANGE 0,00..9,99
(0..20mA)
4 – RANGE 00,0..99,9
(0..20mA)
5 – RANGE 000..999
(0..20mA)
6 – RANGE 0,00..9,99
(4..20mA)
7 – RANGE 00,0..99,9